详情描述

Intrinsically Safe Thermistor AssemblyIntroduction

 

Integrally-mounted explosion-proof resistance thermometers are commonly used with display meters, recording meters, electronic computers, etc., and provide an output of 4-20mA. They directly measure the temperature of liquid, steam, and gas mediums as well as solid surfaces in the range of 0-1800°C across various production processes.

Key Features

Two-wire output of 4-20mA, with strong anti-interference capability.

Save on compensation wire and temperature transmitter installation costs.

Wide measurement range;

Automatic temperature compensation on the cold side, non-linear correction circuit.

Operating Principle

    Integral explosion-proof thermoresistorUsing the gap explosion-proof principle, when an explosion occurs inside the cavity, it can extinguish and cool the fire through the joint surface gap, preventing the temperature of the flame after the explosion from reaching outside the cavity, thus enabling temperature measurement. The thermoelectric potential (resistance) produced by the thermocouple (resistor) generates an unbalanced signal through the bridge of the temperature transmitter, which is then amplified and converted into a 4-20mA DC signal for the working instrument. The working instrument displays the corresponding temperature value.

Technical Specifications

Implementation Standard

   IEC584    IEC1515    IEC751    JB/T5518-91    JB/T7391-94

Temperature Range and Allowable DeviationThermocouple

Model

Pitch number

Allowable Tolerance & Grade of Raw Material

I Grade

II Grade

Tolerance range

Temperature Range: ℃

Tolerance value

Temperature Range: °C

WRNB

K

±1.5℃

-40~+375

±2.5℃

-40~+333

±0.004│t│

375~1000

±0.0075│t│

333~1200

WRMB

N

±1.5℃

-40~+375

±2.5℃

-40~+333

±0.004│t│

375~1000

±0.0075│t│

333~1200

WREB

E

±1.5℃

-40~+375

±1.5℃

-40~+333

±0.004│t│

375~800

±0.004│t│

333~900

WRFB

J

±1.5℃

-40~+375

±1.5℃

-40~+333

±0.004│t│

375~750

±0.004│t│

333~750

WRCB

T

±1.5℃

-40-~+125

±1℃

-40~+333

±0.004│t│

125~350

±0.0075│t│

133~350

WRPB

S

±1℃

0~+1100

±2.5℃

0~600

±[1+0.003(t-1100)]

1100~1600

±0.0025│t│

600~1600


Note: t represents the absolute value of the measured temperature of the thermosensitive element.

Temperature Measurement Range and Tolerance (Thermistor)

Model

Pitch number

Temperature Range: °C

Precision Grade

Permitted deviation

WZPB

Pt100

-200~+500

Grade A

±(0.15+0.002|t|)

Grade B

±(0.30+0.005|t|)

WZCB

Cu50

-50~+100

-

±(0.30+0.006|t|)

Cu100

Note: t represents the absolute value of the measured temperature of the thermosensitive element.

Ex-proof rating:

Airtight: dIIBT4, dIICT5, dIICT6

Intrinsic Safety Type: iaIICT6

Other Parameters

Output Signal: 4-20mA, Load Resistance: 250Ω, Transmission Wire Resistance: 100Ω

Output Method: Binary System

Tolerance Grades: 0.1; 0.2; 0.5

Power Supply: 24V.DC ±10%

Protection Level: IP65

Thermal Response Time

When there is a step change in temperature, the current output signal of the instrument changes to 50% of the step change required time, usually represented as τ0.5. If the step response stability time of the temperature transmitter does not exceed one-fifth of the thermal response stability time τ0.5 of the thermocouple (resistor), then the thermal response time of the thermocouple (resistor) is used as the instrument's thermal response time.

When the settling time of the temperature transmitter's step response does not exceed half of the thermocouple (resistance) thermal response settling time τ0.5, then use the temperature transmitter's thermal response time as the instrument's thermal response time.

询价单