LRD-3051AP Differential Pressure Transmitter
Technical Specifications:
Migration Amount: After positive and negative migration, the upper and lower limits of the range must not exceed the range limits. The maximum positive migration amount is 500% of the minimum adjustment range.
Overpressure Limit: Applies 0 (absolute pressure) to 13.7 MPa without damaging the pressure transmitter; flange can withstand 68.9 MPa of pressure. Normal operating pressure greater than 3.45 kPa (absolute pressure)
Temperature Influence: Maximum Range, Zero Point Error ±0.5%/55℃ (i.e., within the range of 0-0.117~0.69MPa, including the range and zero point total error ±1.0%/55℃)
Minimum measurement range, zero-point error is 3.0%/55 (i.e., 0-0.117~0.69 MPa, including 0-0.117 MPa), total error of range and zero point is ±3.5%/55℃.
Note: The temperature error for the range of 3 should be doubled.
Installation Position Impact: Can cause a maximum zero-point error of ±0.25 kPa, which is adjustable and does not affect the range. No impact on the relative rotation of the measuring body with respect to the flange.
Weight: 5.4 kg (excluding options)