Cosel UPS batteries utilize an automatic safety valve (VRLA) to prevent gas inhalation into the battery, affecting its performance, and also to avoid damage to the battery due to abnormal internal pressure caused by gases produced during charging, etc. The fully enclosed batteries do not emit electrolyte or acid mist under normal float charging. Additionally, the batteries are paired with battery trays using proprietary patented technology, ensuring safer use of the battery assembly.
Key Product Features
No maintenance required
Utilizing the exclusive gas recombination technology (GAS RECOMBINATION). No need for regular liquid topping up and maintenance, alleviating user concerns post-purchase.
High safety and reliability
Utilizing an automatically operable safety valve (VRLA) prevents gas from being吸入 into the battery, affecting its performance, and also safeguards against internal pressure damage caused by gases produced during charging. Furthermore, under normal float charging, there is no electrolyte or acid mist discharge. Additionally, the battery tray, using our proprietary technology, is designed for use with the batteries to ensure safer battery assembly operation.
Long service life
At 20°C, the float life of FM series small sealed batteries is up to 3-5 years, the float life of FM fixed sealed batteries is up to 8-10 years, the float life of FML series batteries is up to 10 years, the float life of FMH series batteries is up to 10 years, the float life of GFM series and solar deep cycle series batteries is up to 15 years, and the float life of GFMJ series batteries is up to 18 years.
Low self-discharge rate
Utilizing lead calcium alloy, the self-discharge rate of the battery is reduced. Under an ambient temperature of 20°C, Cosda's batteries can be used normally without needing to recharge for 6 months.
High conductivity
Utilizing silver-plated copper core terminals and special design ensures electrical performance.
Strong directional characteristics
Special separator (AGM) securely absorbs the electrolyte, preventing it from flowing. The battery will not leak whether it is standing or lying down, ensuring normal operation.
Highly adaptable to environments; pollution-free
Operable in ambient temperatures ranging from -20°C to +50°C, suitable for desert and alpine climates. Can be used with special power supplies for explosion-proof areas.
Battery rooms do not require acid-resistant and corrosion-preventive measures and can be housed in the same room as electronic instruments and equipment.
Technical Specifications
Battery Capacity: 33AH~250AH.
2. Battery Characteristics: Standard series, float charge life up to 8-10 years.
3. Application Range: UPS/Communication/Electricity (standard with leak-proof safety patented tray).
| Model | Rated Voltage (V) | Rated Capacity (AH) | Dimensions (mm) | Reference Weight (KG) | Terminal Type | |||||
| 10HR | 5HR | 1HR | Long | Wide | High | Overall Height | ||||
| 1.80V/C | 1.8V/C | 1.75V/C | ||||||||
| 3-FML-100 | 6 | 100 | 85 | 60 | 195 | 170 | 206 | 210 | 16 | M2 |
| 3-FML-150 | 6 | 150 | 128 | 90 | 260 | 180 | 247 | 250 | 25 | M3 |
| 3-FML-200 | 6 | 200 | 170 | 120 | 323 | 178 | 226 | 231 | 31 | M5 |
| 6-FML-36 | 12 | 36 | 30.6 | 21.6 | 195 | 131 | 155 | 169 | 11.4 | M1 |
| 6-FML-38 | 12 | 38 | 32.3 | 22.8 | 198 | 166 | 170 | 170 | 13.2 | M1 |
| 6-FML-56 | 12 | 56 | 47.6 | 33.6 | 229 | 138 | 212 | 217 | 19 | M1 |
| 6-FML-65 | 12 | 65 | 55.3 | 39 | 350 | 167 | 177 | 177 | 21.5 | M2 |
| 6-FML-85 | 12 | 85 | 72.3 | 51 | 260 | 169 | 211 | 216 | 25 | M1 |
| 6-FML-100 | 12 | 100 | 85 | 60 | 407 | 174 | 208 | 236 | 32.6 | M3 |
| 6-FML-110 | 12 | 110 | 93.5 | 66 | 329 | 172 | 215 | 222 | 33.5 | M5 |
| 6-FML-120 | 12 | 120 | 102 | 72 | 407 | 174 | 208 | 236 | 36.5 | M3 |
| 6-FML-150 | 12 | 150 | 128 | 90 | 532 | 207 | 214 | 221 | 50 | M5 |
| 6-FML-160 | 12 | 160 | 136 | 96 | 341 | 173 | 281 | 288 | 44.5 | M5 |
| 6-FML-200 | 12 | 200 | 170 | 120 | 523 | 240 | 225 | 230 | 62.5 | M3 |
Technical Specifications
Battery Capacity: 38AH~3000AH
2. Solar series with float charge lifespan up to 10-15 years
3. Application Range: Solar Energy Storage Conversion Equipment (Standard with Leak-Proof Safety Patent Tray)
| Number | Model | Rated Voltage (V) | Rated Capacity (AH) | Dimensions (mm) | Reference Weight (KG) | Terminal Type | |||||
| 10HR | 5HR | 1HR | Long | Wide | High | Total Height | |||||
| 1.8V/C | 1.8V/C | 1.75V/C | |||||||||
| 1 | 6-FM-38T | 12 | 38 | 32.3 | 22.8 | 198 | 166 | 170 | 170 | 12 | M1 |
| 2 | 6-FM-65T | 12 | 65 | 55.3 | 39 | 350 | 167 | 177 | 177 | 20 | M2 |
| 3 | 6-FM-100T | 12 | 100 | 85 | 60 | 407 | 174 | 208 | 236 | 32.5 | M3 |
| 4 | 6-FM-150T | 12 | 150 | 128 | 90 | 532 | 207 | 216 | 221 | 47.8 | M3 |
| 5 | 6-FM-200T | 12 | 200 | 170 | 120 | 523 | 240 | 225 | 230 | 57.5 | M3 |
| 6 | GFM200T | 2 | 200 | 180 | 120 | 172 | 111 | 329 | 365 | 13.1 | M3 |
| 7 | GFM300T | 2 | 300 | 270 | 180 | 171 | 151 | 330 | 366 | 18 | M3 |
| 8 | GFM400T | 2 | 400 | 360 | 240 | 210 | 171 | 329 | 363 | 25 | M3 |
| 9 | GFM500T | 2 | 500 | 450 | 300 | 241 | 172 | 331 | 366 | 29 | M3 |
| 10 | GFM600T | 2 | 600 | 540 | 360 | 301 | 175 | 331 | 366 | 35 | M3 |
| 11 | GFM800T | 2 | 800 | 720 | 480 | 410 | 175 | 330 | 365 | 49.5 | M3 |
| 12 | GFM1000T | 2 | 1000 | 900 | 600 | 475 | 175 | 328 | 365 | 56.3 | M3 |
| 13 | GFM1500T | 2 | 1500 | 1350 | 900 | 401 | 351 | 342 | 378 | 92.6 | M3 |
| 14 | GFM2000T | 2 | 2000 | 1800 | 1200 | 491 | 351 | 343 | 383 | 122.5 | M3 |
| 15 | GFM3000T | 2 | 3000 | 2700 | 1800 | 712 | 353 | 341 | 382 | 174 | M3 |