The busway cabinet provides power to the equipment in the data center, including power distribution and protection functions. Generally, it is categorized into three types based on the power nature: AC busway cabinet, low-voltage DC busway cabinet, and high-voltage DC busway cabinet. The busway cabinet is placed at the front of each row of cabinets in the data center, responsible for the power distribution to all rear cabinets and the air conditioning units between rows.
Head cabinet _ Precision Distribution Cabinet Product Parameters
| Project | Parameter value | ||
|---|---|---|---|
| Parameter Name | Communication Header Cabinet | DC cabinet | High-voltage DC string cabinet |
| Input rated voltage | Ac380V | DC48V | DC240V/DC336V |
| Input routes | 1/2 Circuit | ||
| Input rated current | 63A~400A | 160A~1250A | 160A~630A |
| Input Switch | Plastic Shell | Circuit Breaker | Plastic Shell |
| Output Switch | Miniature circuit breakers, output circuits configured according to backend load | Circuit breaker or micro-breaker; the number of output circuits is configured based on the backend load. | DC-specific microbreaker, output circuits based on backend load configuration |
| Input voltage, current power, energy, output branch current, power, energy, switch status (active) | |||
| Lightning Protection Level | C-Level Lightning Protection | ||
| Dimensions | 2200*600*1200mm, compatible with service cabinets (negotiable for customization) | ||
| Appearance Color | Charcoal gray, black, or as per customer's requirement | ||
| In-and-out line method | Upstream and downstream lines, or as per customer requirements | ||
| Installation Method | Freestanding floor-mounted installation ( customizable with casters) | ||