详情描述

I. Overview and Application
 
 The BK, JBKJBK5 series single-phase control transformers are produced by our company over the years using selected materials and advanced technology. They can penetrate deep into the load center. They are mainly used for various machine tool signal indications, control buttons, and safety operation circuits with AC 50-60Hz and voltages not exceeding 1500V. The distribution of various input and output voltages, connection groups, and tap line group capacities of the product can all be carefully designed and manufactured according to customer requirements. They also offer additional advantages such as fire resistance, moisture resistance, safety, energy savings, and convenient maintenance.
 
Two, Product Performance
Name: BK, JBK JBK5 Control Transformer Model: BK, JBK5 (50VA-5000VA) Input Voltage: Single-phase: 110V, 220V, 380V, 450V (Voltage can be customized by customer) Output Voltage: Single-phase: 6.3V, 12V, 24V, 48V, 100V, 110V, 120V, 220V, 230V (Voltage can be customized by customer) Efficiency: 95% Waveform Distortion: No additional waveform distortion Protection: Overcurrent protection, can operate continuously unattended Insulation Resistance: ≥50MΩ Electrical Strength: No breakdown or flashover under 2500V AC sine wave for 1 minute Overload Capacity: Twice the rated current, maintained for 1 minute Environmental Temperature: -15 to +40°C Relative Humidity: <90% Temperature Rise: 155°C (including ambient temperature) Voltage Resistance: 2500V without breakdown Insulation Class: F Class Noise: <60db (one meter away) Size Chart of JBK Series Control Transformers

    Project dimensions and capacitymaxmaxmaxPilot Hole SpacingInstallation HolesStand Foot ThicknessWeight (KG)
    40-6383858956+-0.446+-2.54.8*911.3
    1.9
    100861059464+-0.462+-2.5
    1609810510984+-0.471+-35.8*111.52.6
    3.6
    2509812010984+-0.485+-3
    40012210212590+-0.485+-25.8*925.0
    7.5
    630152112150122+-0.590+-3.57*13
    1000160210151126+-2152+-27*12311
    16
    1600184235163146+-3.5176+-3.5
    2500210265171174+-3.5200+-3.5422

    Product dimensions listed above are for reference only; changes may occur without prior notice. Please understand!
    Note: The installation site must not have significant evaporation of gases that adversely affect transformer insulation, chemical deposits, dust, dirt, and other explosive and corrosive media.
     
    Structure and Features
    BK Transformers can be categorized by structure into shell type, and by installation method into vertical type.
    Model and Specifications

    Input VoltageOutput VoltageModel and SpecificationsDimensionsPilot hole spacingMounting hole
                     
     
     
    220V
    ±10%
     
     
     
    380V
    ±10%
     
     
                     
     
    6V
    12V
    24V
    36V
    110V
    127V
    220V
    380V
    Special voltages available for customization
                    BK-25VA                80                75                90                65×49                5×9
                    BK-50VA                86                86                96                71×58                5×12
                    BK-100VA                98                89                108                83×64                6×12
                    BK-150VA                108                100                108                87×72                6×12
                    BK-200VA                108                110                108                87×83                6×11.5
                    BK-250VA                120                113                130                94×85                9×11.5
                    BK-300VA                116                121                135                97×95                9×11.5
                    BK-400VA                133                138                150                109×100                9×11.5
                    BK-500VA                133                148                150                109×113                9×11.5
                    BK-700VA                146                155                160                123×115                9×11.5
                    BK-1000VA                146                177                165                123×135                9×11.5
                    BK-1500VA                171                200                190                145×135                9×11.5
                    BK-2000VA                180                230                210                145×160                9×11.5
                    BK-2500VA                225                240                225                169×175                9×11.5
                    BK-3000VA                225                240                225                169×175                9×12.5
                    BK-5000VA                283                265                270                215×180                11×13.5

    ■ Usage Instructions

    1. Surrounding air temperature ranges from -25℃ to +40℃, with a 24-hour average not exceeding +35℃.
    2. Installation location altitude not exceeding 2,000 meters.
    3. Relative humidity should not exceed 50% at an air temperature of +40°C, with higher relative humidity permissible at lower temperatures. The average humidity during the wet month is 90%, with a monthly average low temperature of +25°C, considering condensation on the product surface due to temperature changes.
    4. No areas of severe vibration or shock.
    5. Areas not susceptible to rain or snow.
    6. The voltage waveform is approximately sinusoidal.
     
    ■ NotePlease specify: Model, Capacity, Input Voltage, Output Voltage; (To be specified upon order)
    Friendly Reminder: Special voltages available for customization
     


询价单

主题 *
内容 *
Your company's名
Contact person *
ContactPhone *
电子Email
验证码  
 点击确定代表您同意《服务条款》《隐私政策》