详情描述
Sinusoidal Reactor(SWL)Sine Wave Filter
1Product Description
Convert PWM output signals of the motor into a smooth sine wave with low residual ripple voltage to prevent damage to the motor's winding insulation. Reduces the resonance caused by distributed capacitance and inductance due to long cable lengths; eliminates motor overvoltage caused by high dv/dt; reduces early motor failure caused by eddy current losses; the filter lowers the audible noise of the motor.
Sinus Filter is designed to convert the PWM output signal of motor drives a smooth sine wave with low residual ripple so as to avoid the motor insulation damage,reduce the resonance phenomenon caused by the distributed capacitance and inductance due to the long cable, eliminate the excessive motor voltage caused by high dv/dt,eliminate motor damage caused by eddy loss and reduce the noise of motor by filter application.
2Product Features
Utilizes a high-performance foil winding structure with copper busbars, featuring low direct resistance,
High electromagnetic resistance; strong short-term overload capability.
Utilizing high-performance composite insulating materials of F-grade or above.
Maintain reliable performance under harsh working conditions.
The reactor has high insulation strength and can withstand extremely high voltage spikes of Dv/dt.
The reactor uses vacuum pressure impregnation technology, featuring low audible noise.
Due to the excellent foil winding structure and aluminum leading structure, Sinus Filter is characterized by small DC resistance, strong resistance to electromagnetic interference and strong short-time overload capability. F Class insulation materials equip the products with reliable performance even in harsh operating conditions;high insulation ability can sustain high Dv/dt voltage impulse to the reactor; process makes the humming noise low.
3Electrical Diagram

4Technical Specifications
1.Working Voltage: 380VAC-690VAC
2.Working Current: 15A-1500A
3.Operating Frequency: 50/60 Hz.
4.Carrier Frequency: 2K-8K
5.Insulation Class: Class H
6.Pressure Reduction: 8%-12%
9.Operating Environment: -10...+45°C, rated values will not decrease.
10.Protection Level: IP00
11.Maximum Current: 1.5 times rated current, continuous for 60 seconds
12.Noise: <65dB
13.Temperature Rise: ≤75K
14.Dielectric Strength: Core-Winding - 3000VAC/50Hz/5mA/10s no arc-over breakdown (factory tested)
15.Insulation Resistance: >100MΩ at 1000VDC insulation resistance
16.Altitude not exceeding 2,000 meters.
17.Operating temperature: 25℃ to +150℃, relative humidity not exceeding 90%.
18.Surroundings should have good ventilation; if installed in a cabinet, additional ventilation equipment should be added.
1.Work Voltage:220VAC-690VAC
2.Work Current:15A-1500A
3.Work Frequency: 50/60Hz
4.Swltching frequency:2-8KHz
5.Insulation Class: class H
6.Rated voltage drop:8~12%
7.Voltage harmonic distortion:THDU≤5%
8.Load current≤8%
9.Operation Environment:-10~+45 C,rated value wont’t lower,when higer than 55 ℃and every lc,the current will step down 2%
10.Protectlon class:IP00-lP22
11.Max Current: 1.5 xRated current,continuous 60S
12.Noise:≤ 65dB
13.Temperature Rise:75K
14.Dlelectric strength: Core Col 3000VAC/50Hz/5mA/10s no electric arcing puncture (factory test)
16.Under seal level 2000m
17.Running temperature 25 ℃-+150 ℃,comparative malsfure not over 90%.
18.With well-ventilated condition,ventilation devices shall be mounfed if installatioh in panels











