Product Features and Applications
This product is suitable for subways, high-rise buildings, shopping malls, theaters, power stations, chemical factories, city squares, and other public utilities that require high flame-retardant properties for cables, with rated voltages of 450/750V and below.
WDZ-RYY Low Smoke Halogen-Free Flame Retardant Cable, WDZN-RYY Low Smoke Halogen-Free Flame Retardant and Fireproof Flexible Cable
Halogen-free and low-smoke cables have slow flame spread, low smoke concentration, high visibility, and minimal release of harmful gases during a fire, making it easier for people to evacuate.
Low corrosiveness of the combustion gases also prevents damage to instruments and equipment. The low halogen and halogen-free properties significantly enhance the cable material's resistance to aging and ultraviolet radiation, as well as other radiations, thereby extending the service life of the cables.
Low-Smoke, Halogen-Free Flame Retardant Cable WDZ-RYY WDZ-RYYP
Product Execution Standard
GB9330-88 Q/WTL11-2003
Utilize features
Cable rated voltage UO/U: 450/750V, AC polyolefin UO/U: 0.6/1KV
2. The long-term working temperature of the cable is: -20℃ to 90℃, -40℃ to 105℃
3. Recommended bending radius: Unarmored cables should not be less than 6 times the cable's outer diameter, while armored or copper tape structured cables should not be less than 12 times the cable's outer diameter.
Key Technical Specifications
Cables should withstand a 3kV AC voltage test under environmental temperature for 5 minutes without puncturing.
2. The cable's light transmittance should comply with the table below.
Outer Diameter of Cable D (mm) Transparency (%) ≥ Outer Diameter of Cable D (mm) Transparency (%) ≥ D > 4070 5 < d ≤ 10 5 < d ≤ 40 6 ≥ d
3. Non-flammability of cables (fire-retardant properties): Should pass the B-class bundle combustion test as specified in GB12666.5-90. The vertical combustion test for a single cable should pass GB12666.2-90.
4. Halogen acid gas emission, conforms to IEC 754-1
5. The pH value and conductivity of the combustion gas meet IEC 754-2 standards: pH ≥ 4.3, conductivity ≤ 10 μS/mm.
Low-smoke halogen-free flame-retardant cable WDZ-RYY, WDZ-RYYP
WDZ-RYY Low Smoke Halogen-Free Flame Retardant Cable, WDZN-RYY Low Smoke Halogen-Free Flame Retardant Fireproof Soft Cable, Halogen-Free Cable, Environmental Cable, WDZ-RYYP
Low-smoke, halogen-free cables are environmentally friendly cables made from rubber that does not contain halogens (F, Cl, Br, I, At), lead, cadmium, and chromium, etc., which do not emit toxic smoke when burned.
Halogen pointers: All halogen values ≤ 50PPM (as per regulation PREN 14582)
The product, after combustion in a sealed container, has a light transmittance of ≥60% through a beam of light (in accordance with EN-50268-2 regulations).
Pb < 90PPM, Cd, Cr6+, Hg, PBBs, PBDEs all < 5PPM
Application: This product boasts excellent flame-retardant properties, emits minimal smoke during combustion, and does not release corrosive gases. It is widely used in nuclear power plants, subway stations, telephone exchanges, computer control centers, high-rise buildings, hotels, broadcasting and television stations, oil platforms, and other locations with high human concentration and low air density.