Vertical Burning Test Apparatus for Single Conductor Cable
Vertical burning test instrument for single-core wire and cable is suitable for research, production, and quality inspection departments of lighting equipment, low-voltage electrical appliances, household appliances, machine tool electrical equipment, motors, electric tools, electronic instruments, electrical measuring instruments, electrical connectors and accessories, electrical and electronic products, and their components.
The testing instrument employsThe product structures recommended in the section on air-mixed gas construction of GB18380.12-2008 fully meet the acceptance requirements of quality inspection authorities. Standards: GB/T18380.1-2008, GB/T18380.11-2008, GB/T18380.12-2008, GB/T18380.21-2008, GB/T18380.22-2008, GB/T19666-2005, GB12972, GB3003, IEC60332, MT818, MT386, ISO5656.
Vertical combustion test for single-core wire and cable is conducted using a specified size Bunsen burner and a specific gas source (propane), applying flame at a certain height and an equal ignition angle to the specimen in a vertical position over a timed period. The flammability and ignition hazard are evaluated based on the time to ignition, duration of combustion, and length of the flame.
Technical Specifications
1、Color Screen Controller: Automatically records test time, displays results, times, automatically ignites, and returns the Bunsen burner to its original position. Optional to turn off gas.
2、Burner: Inner DiameterΦ9.5mm±0.5mm
3、Test Angle:The 45° specimen beam is movable, adjustable according to the thickness of the specimen to the position of the Bunsen burner.
4、Flame Height:20mm ± 2mm to 190mm ± 1mm adjustable
5、Application Time:0 to 999.9 seconds ±0.1 second adjustable
6、Combustible gases:95% purity propane gas (can be substituted with liquefied gas in most cases)
7、Ambient Temperature:23℃±10℃
8、Sample Length:600mm±25mm
9、Sample Diameter: Should be greater than0.8mm
10、Burner Torch Power:1kw
11、Voltage:220v/50Hz
12、Gas Flow Rate:0~1L/min
13、Airflow:1.5~15L/min
14、Dimensions:60cm×45cm×156cm
Standard recommendations for two flame calibration methods
1、Flame core50-60mm, outer flame 170-190mm
2、10g copper head takes 45s ±5s to heat from 100℃ to 700℃